DLSB series low temperature Cooling Liquid Circulating Pump adds the circulating water pump on the basis of the refrigeration. The new design is elegant and the circulation system is made of stainless steel, with anti-corrosion, anti-rust, anti-cold liquid pollution and other properties.
What are the Types of Chillers?
There are several types of chillers, including the water-cooled chiller, air-cooled chiller, and evaporation cooled chiller. These different kinds of chillers have different characteristics, advantages and disadvantages. Water-cooled systems can offer a high efficiency and environmental impact advantages over air-cooled systems.
How does a Chiller Work?
A chiller consists of the usual evaporator, condenser, compressor, and expansion device set up. The working process of a chiller can be simply described below. A chiller can cool water or oher fluids, which are used to cool equipment. After absorbing heat from what is being cooled, the water or other fluids can go through the chiller. In the chiller, the heat is transferrred from the fluid to the ambient air.
Some Tips on Using a Chiller
1. All operators should read this specification before proceeding;
2. If it is not specified as “explosion-proof” type, this equipment is not suitable in flammable and explosive workplaces.
3. This equipment is not used in places where the environment is rotted seriously;
4. Strong magnetic fields may affect the normal operation of the machine, so the device is not suitable for environments with strong magnetic fields;
5.This equipment allows the working environment temperature range of 5 ° C ~ 30 ° C, humidity ≤ 85%, beyond this range will affect the safety and usage performance of the equipment.
Next, I will introduce the latest Low Temperature Cooling Liquid Circulating Pump:
DLSB-5/10Low Temperature Cooling Liquid Circulating Pump Introduction
1.DLSB-5/10Low Temperature Cooling Liquid Circulating Pump
DLSB-5 series low-temperature cooling liquid circulating pump, also known as low temperature pump, low temperature circulating pump, low temperature cooling water circulating pump, water tank volume is 5L, min no-load temperature is between -15℃~-123℃, best environment temperature is 5℃~25℃.

Product Advantages:
1.The circulation system is made of stainless steel and has anti-corrosion and anti-rust functions.
2. Imported air-cooled fully enclosed compressor unit with advanced performance and reliable quality.
3. Digital display constant temperature display, microcomputer temperature control, simple operation.
DLSB-20/30Low Temperature Cooling Liquid Circulating Pump Introduction
2.DLSB-20/30Low Temperature Cooling Liquid Circulating Pump
DLSB-20 series low-temperature cooling liquid circulating pump, also known as low temperature pump, low temperature circulating pump, low temperature cooling water circulating pump, water tank volume is 10L, min no-load temperature is between -15℃~-122℃, best working environment is 5℃~25℃. DLSB-20 series of low-temperature cooling liquid circulating pump is a low temperature liquid refrigerant equipment which takes mechanical forms to refrigerate. It has the function of providing a cryogenic liquid, low temperature water bath. It can be combined with the rotary evaporator, glass reactor, vacuum freezing drying oven, circulating water vacuum pump, magnetic stirrer and other instruments to proceed multi-functional chemical reaction or store drugs under low temperature condition.
Product Advantages:
1.The circulation system is made of stainless steel and has anti-corrosion and anti-rust functions.
2. Imported air-cooled fully enclosed compressor unit with advanced performance and reliable quality.
3. Digital display constant temperature display, microcomputer temperature control, simple operation.
DLSB-50/30Low Temperature Cooling Liquid Circulating Pump Introduction
3.DLSB-50/30Low Temperature Cooling Liquid Circulating Pump
DLSB-50 series low-temperature cooling liquid circulating pump, also known as low temperature pump, low temperature circulating pump, low temperature cooling water circulating pump, water tank volume is 50L, min no-load temperature is between -23℃~-120℃, best working environment is -10℃~-120℃. The circulating water pump is added on the basis of refrigeration, which enables the cooled liquid to go through the pipeline for external and internal circulation. It can provide cryogenic liquid for external equipment such as double-layer glass reactor, organic synthesis device and rotary evaporator.It can be combined with the rotary evaporator, glass reactor, vacuum freezing drying oven, circulating water vacuum pump, magnetic stirrer and other instruments to proceed multi-functional chemical reaction or store drugs under low temperature condition.
Product Advantages:
1.The circulation system is made of stainless steel and has anti-corrosion and anti-rust functions.
2. Imported air-cooled fully enclosed compressor unit with advanced performance and reliable quality
3. Digital display constant temperature display, microcomputer temperature control, simple operation
Laboratory Low temperature cooling liquid water circulating pump DLSB 5L/-10℃ test machine:
Matching Products
Troubleshooting:
1 | The whole machine has no electricity | No power supply | Check the power supply |
Circuit breaker protection | Reset circuit breaker | ||
Fuse burn | Replace fuse | ||
Power line off | Tighten the power line | ||
Wrong phase sequence of power supply | Adjust the position of two fire wires at will | ||
2 | No temperature display | No temperature display | Turn on the power switch |
Display board line off | Plug in the sensor socket | ||
Water splashed on the circuit board | Dry or sun dry before starting | ||
3 | Display on the □□□□or EO | Sensor break | Plug in the sensor socket |
Sensor short circuit | Replace the sensor | ||
4 | Display on the □□□□or EO | Sensor short circuit | Replace the sensor |
5 | Display does not match the actual | Sensor off | Reinstall and tighten |
6 | Temperature control disorder | Voltage instability | Stabilize the voltage before starting up |
The temperature control circuit is broken | Replace the temperature control circuit | ||
7 | No cooling or slow cooling | System leakage | Please have it repaired by a professional |
8 | The machine stops when the temperature does not reach the set value | The temperature control circuit is broken | Replace the temperature control circuit |
Compressor overheating protection | Improve ventilation and start after cooling | ||
9 | No exhaust air | Fan power cord is not in good contact | Connect the power wire |
Fan stuck | Adjust fan position | ||
The wind leaf deformation | Replace the new fan | ||
Fan burn out | Replace the new fan | ||
10 | The compressor is not working but there is a click | Starting capacitor breakdown | Replace capacitors of the same type |
Compressor is bad | Replace compressor of the same type | ||
11 | No external loop | Power line off | Tighten the power line |
The water inlet is blocked | Remove the blockage | ||
Adjustment valve is not open | Open the adjustment valve | ||
There is ice blocking in the circulating pump | Shut down and thaw | ||
12 | Fuse burn | Start capacitor burnout | Replace capacitors of the same type |
There is a short circuit | Check each line |